CALL
FOR SPECIAL PRICING
KD100V
Our industrial generators are ideally suited for use at factories, schools,
hospitals and other facilities requiring dependable standby power.
With a closed circuit, pressurized cooling system and ambient temperature rating
of 40 degrees C (104ºF), the KD100V generates 125kVA/100kW standby power and
112.5kVA/90kW prime power at 60 Hertz. The generator is offered as a skid-mount
or sub-base tank mount design, integral vibration isolators and the choice of
weather-protective housing or sound-attenuated housing designs
|
Specifications |
| Performance
Data |
| Amps - Single Phase 120V |
275 |
| Amps - Three Phase - 240V |
301 |
| Amps - Three Phase - 480V |
150 |
| Voltage Regulation - no
load to full load |
+/- 1% |
| Maximum Amps @ 120V |
347 |
| Maximum Amps @ 240V |
301 |
| Power Source |
| Displacement cu. in (cc): |
290 |
| Bore x Stroke (mm) |
4.25 (108) x 5.12 (130) |
| Fuel Consumption - full
load - gph (lph): |
7.1 (26.8) |
| Fuel Consumption - 3/4
load - gph (lph): |
5.3 (20.1) |
| Fuel Consumption -1/2
load - gph (lph): |
3.7 (14) |
| Fuel Consumption - 1/4
load - gph (lph): |
2.3 (8.6) |
| Engine Model |
TAD520GE 4-cycle,
turbochar |
| Fuel Type |
Diesel |
| Engine Make |
Volvo |
| Engine RPM |
1,800 |
| Dimensions |
| Wet Weight lbs. (kg): |
2,460 (1,116) |
| Dry Weight lbs. (kg): |
2,392 (1,085) |
MultiQuip KD Industrial Generators Options
Requires
Adobe Acrobat Reader
|