CALL FOR SPECIAL PRICING
The EGC-1000C has a standby rating of 1000 kW and a prime rating of 900 kW. It provides excellent steady-state voltage regulation of 0.25 percent, no load to full load. Enclosed in a sound attenuated 40-foot container, the generator has its own control room that provides the operator with clear, concise performance information. The generator is powered by a turbocharged and aftercooled engine that meets EPA Tier 2 emissions standards.
Specifications | |
---|---|
Model | EGC-1000C |
Prime Output KW (KVA): | 900 KW (1125 KVA) @ 60Hz |
Frequency: | 60Hz or 50Hz |
Voltage Regulation - no load to full load | + / - 0.05 percent |
Generator Design: | Revolving Field, PMG |
Frequency Regulation - no load to full load: | Isochronous |
Frequency Regulation - steady state | + / - 0.25 percent |
Displacement cu. in (cc): | 1,944 (31,856) |
Fuel Consumption - full load - gph (lph): | 78.2 (296) |
Fuel Consumption - 3/4 load - gph (lph): | 53.4 (202.1) |
Fuel Consumption - 1/2 load - gph (lph): | 36.7 (138.9) |
Fuel Consumption - 1/4 load - gph (lph): | 20.5 (77.6) |
Fuel Tank Capacity - gal (liters): | 376 (1,423) |
Engine Design: | Turbocharged, Air to Water Aftercooler |
Engine Model: | 16V2000/G81 |
Engine HP; rpm | 1495; 1800 |
Engine Make: | Detroit Diesel |
No. Cylinders: | 16 |
Notice: Features and equipment specifications are subject to change without notice.
|